INSULATING PLASTIC GUARDS/ COVERS
LINE HOSES/ COVERS
ARC FLASH PPE
DIELECTRIC FOOTWEAR
INSULATED JUMPERS
VOLTAGE DETECTORS
INSULATED TOOLS
OUTAGE PROTECTION
SLEEVES
BLANKETS
HISTORY
CONTENT
GROUNDING
SAFETYLINE
HOT STICKS
INSULATORS
GLOVES
DESIGN Unibody design insulators are one-piece injection molded directly to the rod and sealed to the end fittings with a bead of silicone to give the insulator high dielectric strength and protect it from all environmental conditions. This design is used for standard distribution dead end/suspension insulators. FIBERGLASS ROD A high quality fiberglass reinforced rod is the core of every insulator with ultimate mechanical strength at least twice the maximum working load. END FITTINGS Standard distribution dead/end suspension units are supplied with clevis and tongue fittings meeting ANSI C29 specifications. Ball, socket and eye fittings are also available. All are made of hot dipped galvanized high strength carbon steel and have an ultimate tensile strength rating of 15,000 pounds. All end fittings on dead/end suspension insulators are attached by compression. Every insulator ls proof tested to verify the crimp.
Unibody insulators have end fittings sealed with silicone to eliminate any possibility of moisture or contamination from reaching the fiberglass rod.
188
189
INSULATORS SPECIFICATIONS Dimensions Rated Voltage
15 KV
25 KV
35 KV
Section Length Leakage Distance
345 mm ±15 mm 430 mm ±35 mm 525 mm ±55 mm
430 mm 210 mm
640 mm 301 mm
850 mm 398 mm
Minimum Arcing Distance Electrical Ratings Low Frequency Flashover
Dry
100
131
166
INSULATORS SILICONE COMPOSITE INSULATORS We combine the technologies of a fiberglass reinforced rod, metal fittings and our extensive knowledge of elastomeric insulation to produce a high quality composite insulator. Since 1980, thousands of silicone insulators have been installed by utilities worldwide in a variety of environments. Continued outstanding performance is proof of their superior quality and design.
Voltage Test (60 Hz)
Wet
82 kV
111 kV
138 kV
Critical Impulse Flashover
Positive
159
221
279
Voltage Test
Negative
185 kV
251 kV < 1 μ V
320 kV < 1 μ V
Radio Influence Voltage Data Max. Voltage < 1 μ V
Mechanical Ratings Failing Load Test
> 7000 KG
> 7000 KG
> 7000 KG
Number of Sheds
4
6
8