There are a variety of Fiberglass Reinforced Plastic (FRP) constructions used for hotsticks. Included are foam filled tubular sticks used for all products requiring solid construction. All Salisbury fiberglass sticks meet ASTM F711 Standard Specifications for FRP and tubes used in live line tools and IEC 855. Foam filled hotsticks are manufactured using the pultrusion process. This method incorporates fiberglass reinforcement in a resin matrix which creates a moisture resistant laminate with excellent electrical and mechanical properties. FIBERGLASS HOTSTICKS Standard Specifications

LIVE LINE WORK MINIMUM APPROACH DISTANCE Nominal Voltage (kV) Phase-to-Phase Distance: ft in (m)

Phase-to-Ground Exposure Phase-to-Phase Exposure

160

161

0.05 to 0.3

avoid contact

avoid contact

0.301 to 0.75 0.751 to 5 5.1 to 15 15.1 to 36 36.1 to 46 46.1 to 72.5 72.6 to 121 121.1 to 145 145.1 to 169 169.1 to 242 242.1 to 362 362.1 to 420 420.1 to 550 550.1 to 800

1 ft 1 in (0.33 m)

1 ft 1 in (0.33 m)

2 ft 0.8125 in (0.63 m)

2 ft 0.8125 in (0.63 m)

2 ft 1 in (0.65 m) 2 ft 6 in (0.77 m) 2 ft 9 in (0.84 m)

2 ft 2 in (0.68 m)

2 ft 11 in (0.89 m) 3 ft 2 in (0.98 m) 3 ft 11 in (1.2 m)

3 ft 3 in (1 m)

Distance: ft in (m) Phase-to-Ground Exposure Phase-to-Phase Exposure

Voltage Range Phase-to-Phase (kV)

3 ft 8 in (1.13 m)

4 ft 7 in (1.42 m) 5 ft 4 in (1.64 m) 6 ft 4 in (1.94 m) 10 ft 1 in (3.08 m) 18 ft 1 in (5.52 m) 22 ft 4 in (6.81 m)

Hot sticks and switch sticks from Salisbury are engineered to keep utility workers safe when they are on the line. Salisbury hot sticks feature closed cell foam filled fiberglass handles and are engineered to meet or exceed ASTM F711 safety standards and utilize premium materials for both safety and tool durability. Salisbury is recognized globally for its manufacturing of personal protective equipment and live line tools to protect electrical workers from the hazards of their job. HOTSTICKS & TOOLS

4 ft 3 in (1.3 m)

Foam filled Hotsticks

FAQ Q: Are rescue sticks required to be periodically electrically tested? A: Yes, see OS HA 1910.269(j) for specific testing requirements. Hotstick production is 100% electrically proof tested. Hotstick blanks must pass a test of 100 kV/12 in (305 mm) for 5 minutes without detectable heating prior to being accepted. Hot Stick blanks conform with ASTM F711 requirements.

4 ft 9 in (1.46 m) 6 ft 7 in (2.01 m) 11 ft 2 in (3.41 m) 13 ft 11 in (4.25 m) 16 ft 7 in (5.07 m) 22 ft 6 in (6.88 m)

27 ft 0.375 in (8.24 m)

37 ft 4 in (11.38 m)

These distances take into consideration the highest switch surge an employee will be exposed to on any system with air as the insulating medium and the maximum voltage shown.

The clear live-line total distances shall equal or exceed the values for the indicated voltage ranges.